Skip to main content

SolaX - X3 ULTRA

Configuration Guide for SolaX X3 ULTRA Series: 15K, 15KP, 19.9K, 20K, 20KP, 25K, 30K

Written by Marija Gelmanovska

Before you start

Before you begin, make sure:

  • The inverter is physically installed and powered on

  • You have the Solax pocket WiFi+LAN dongle

  • All assets (inverter, Solax pocket WiFi+LAN dongle) are updated to the latest software version


Step-by-Step Instructions

1. Connect the inverter to the network

  1. Plug the pocket WiFi+LAN dongle into terminal E on the inverter

  2. Connect the dongle to your local network with an Ethernet cable

  3. Verify the connection is established by checking the LED on the dongle or in the SolaXCloud app

image

For network infrastructure requirements and troubleshooting, see Infrastructure requirements for the gateway.

2. Plug&Play discovery and configuration

This inverter supports Plug&Play, requiring no manual configuration. It is automatically detected during gateway commissioning and configured with the appropriate settings after connection.

3. Discover the inverter in the commissioning wizard

The inverter is now ready for the commissioning wizard. The gateway will scan the network to find available devices, which may take a few minutes. Once complete, the Solax X3 Ultra inverter will appear on the results page.

When the inverter is detected, in most cases set the asset type to Hybrid (PV and Battery) from the dropdown.

If you are using the inverter exclusively as a PV inverter, select PV System. If it is used solely as a battery inverter, choose Battery.


Country-specific configurations

Germany

Applies to PV installations exceeding 2 kWp installed after February 24, 2025.

For detailed information refer to §9 EEG (2025) – 60% feed-in limitation

No additional inverter configuration is required. The gateway controls the inverter directly (PV Limit), supporting energy management optimization.

Set the following Energy management setting in the commissioning wizard:

  • Allow optimisation: Yes

  • Grid feed-in limit controlled by inverter: No


FAQ

Why isn't the inverter appearing in the commissioning wizard?

Check that the pocket WiFi+LAN dongle is properly inserted into terminal E on the inverter and connected to your network with an Ethernet cable. Restart the gateway and wait for the network scan to complete.

How do I update the firmware of the inverter?

Download the latest firmware from the SolaX website or contact SolaX Service Support to obtain firmware files. The update is performed by inserting a USB stick into the inverter's upgrade port.
For detailed update instructions, refer to the official SolaX documentation.

Where is the dongle terminal on the inverter?

Terminal E is labeled on the inverter. Check your inverter's documentation for its exact location.

Do I need to configure Modbus settings?

No, this inverter connects automatically via Modbus TCP once the dongle is properly connected.


Supported models

  • X3-ULT-15K

  • X3-ULT-15KP

  • X3-ULT-19.9K

  • X3-ULT-20K

  • X3-ULT-20KP

  • X3-ULT-25K

  • X3-ULT-30K

Did this answer your question?