General context and relevance of §9 EEG
Each of the following criteria must be fulfilled to be relevant according to §9 EEG "Solar peak amendment" (Solarspitzengesetz):
new PV installation in Germany and the installation date after 24.2.2025
including PV installation with peak power above 2 kW
For systems that meet both criteria, §9 EEG is automatically enabled and cannot be disabled. The operator (homeowner) must ensure that the grid feed-in is limited to 60% of the PV installation's peak power (PV module capacity), unless an SMGW + Steuerbox is installed and successfully tested for this household.
The configuration steps below are required for §9 EEG to function correctly. If either the EMS (configured via the commissioning wizard) or the inverter is not configured as described, §9 EEG remains active but will not enforce the feed-in limitation. The system will be non-compliant.
§9 EEG configuration instructions by inverter
For each supported inverter, open its commissioning article and follow the Country-specific configurations → Germany section.
Inverters controlled via GCP Limit
The system is limited by the inverter using the grid connection point as reference; EMS is steering all other controllable assets accordingly
Inverters controlled via PV Limit
The system is controlled by the EMS, which limits the inverter's PV output (DC side).
Important
For inverters that the EMS cannot control, the 60% feed-in limitation must be configured manually — directly on the inverter or via the manufacturer's configuration software. See the respective manufacturer's documentation for instructions.
The relevant models show Not Supported for Controlling HEMS in the Supported Assets list. Support is subject to change. Please check regularly for updates.
If an inverter manufacturer, series, or model is not listed at all, contact customer support.
FAQ
Can multiple inverters be combined? (BETA)
Multiple inverters that require §9 EEG can be combined. However, only one of the inverters may have a battery; multiple batteries are not supported.
If multiple GCP Limit inverters are combined, each needs a meter at the GCP.
