Skip to main content

my-PV - AC-THOR

Configuration Guide for AC-Thor

Written by Marija Gelmanovska

Before you start

Before you begin, make sure:

  • The AC-THOR heating rod is physically installed and powered in a water tank according to manufacturer requirements

  • The AC-THOR is updated to the latest software version

  • One temperature sensor is connected

  • The device will be used in Mode 1 - Hot water only

  • The my-PV Web GUI is installed on your device

IMPORTANT: A maximum of 1 my-PV heating device in Mode 1 - Hot water can be used per system and gateway. The connection of several devices and the master-slave function are not supported and can lead to incorrect control of the energy flows.

DANGER: Using the heating rod when not installed can cause damage to the device and injuries due to hot surfaces. Wrong values can cause harm to people and might potentially damage your heating system.


Step-by-Step Instructions

1. Connect the AC-THOR to the network

  1. Connect an Ethernet cable to the Ethernet port of the AC-THOR

  2. Verify the connection is established by checking the device display

For network infrastructure requirements and troubleshooting, see Infrastructure requirements for the gateway gateway.

2. Access the heating rod settings

The IP address of the heating rod can be found via the info section on the display of the unit

  1. Open the my-PV Web GUI

  2. Enter the IP address to login

  3. Ensure that the Device state is set to On

3. Enable communication via Modbus

  1. Navigate to:
    Control settings

  2. Configure the following Modbus settings:

    • Control type: Modbus TCP

    • Power time out: 30 seconds

  3. Save the settings

4. Configure hot water settings

Mode settings

When using the AC-THOR in conjunction with a gateway, you can only use Mode 1 with one temperature sensor.

  1. Navigate to:
    Mode settings

  2. Configure the following settings:

    • Mode: 1: Hot water 3kW

  3. Click Save the settings

Hot water settings

  1. Navigate to:
    Hot Water

  2. Configure the following settings:

    • Temperature max. - Solar powered: Enter the maximum technical temperature for the installed hot water system

    • Boost mode: Deactivate

  3. Click Save the settings

Important: Deactivate the boost mode to ensure correct control of the energy management. You can set the minimum temperature within the energy management application which then is valid at all times, even without surplus power/through grid supply.

Legionella protection (optional)

Activate legionella protection in the web portal to periodically heat the water to at least 60°C. During legionella heating cycles, the AC-THOR is not controlled by the gateway.

5. Discover the heating rod in the commissioning wizard

The heating rod is now ready for the commissioning wizard. The gateway will scan the network to find available devices, which may take a few minutes. Once complete, the my-PV AC-THOR will appear on the results page.

6. Configure temperature settings in the commissioning wizard

After the scan completes and the AC-THOR is discovered, proceed through the commissioning wizard to the Heating Rod configuration step. Configure the three temperature thresholds:

  • Maximum temperature: Upper heating limit with PV surplus. Recommended: 80°C for space heating, max. 60°C at tap for domestic hot water. If the heating element has a thermostat, set it to the same value.

  • Comfort temperature: Above this value, only PV surplus is used for heating. Recommended: ca. 10°C below maximum temperature.

  • Minimum temperature: Below this value, grid supply is used as backup. Recommended: min. 10°C for frost protection; if the heating rod is the primary heat source, follow the heating installer's recommendation.


FAQ

Why isn't the heating rod appearing in the commissioning wizard?

Check that the AC-THOR is connected via Ethernet and that Modbus TCP is enabled (Control type: Modbus TCP, Power time out: 30 seconds). Verify the device state is "On" and Mode 1 is selected. Check that the temperature sensor is properly connected. Restart the gateway and wait for the network scan to complete.

How do I update the firmware of the AC-THOR?

Download the latest firmware from the my-PV website and perform the update through the Web GUI.
For detailed update instructions, refer to the official my-PV documentation.

Where can I download the my-PV Web GUI?

The my-PV Web GUI is not available in an app store. Download it from the my-PV website.

Why can't the Web GUI find my device?

Find the IP address of the AC-THOR via the info section on the display. If the device still doesn't appear, manually enter the IP address in the Web GUI to connect.

Why is the load status showing 0 instead of 1?

If the load status shows 0, the circuit is not closed. This could be caused by a thermostat that is switched off or a safety temperature limiter that is triggered. Check the wiring and thermoswitch if installed.

Why isn't the temperature sensor reading showing?

If no temperature is displayed at Temperature sensor 1, check the physical connections. Error codes: 0°C indicates a broken probe, 85°C indicates data disruption from the temperature sensor.

Can I use the AC-THOR in a mode other than Mode 1?

No. When using the AC-THOR in conjunction with a gateway, you can only use Mode 1 - Hot water with one temperature sensor.

Can I connect multiple my-PV devices to one gateway?

No. A maximum of 1 my-PV heating device can be used per system and gateway. The connection of several devices and the master-slave function are not supported and can lead to incorrect control of the energy flows.

How do I verify the hardware connections are correct?

Navigate to the status page by clicking the status page button and review the state information values:

  • Load status: Each phase should show 1 (OK). A value of 0 means the circuit is not closed — check the wiring and thermoswitch if installed

  • Load nominal power: Should match the rated power of the connected heating rod according to the hardware specs

  • Temperature sensor 1: Should display the current temperature. Error codes: 0°C = broken probe, 85°C = data disruption

What thermostat temperature should I set on the heating rod?

Set the thermostat of the connected heating rod ideally to 80°C. If the system cannot sustain 80°C (due to pipes, seals, or tank limitations), set it as close to 80°C as possible. After commissioning, set the maximum temperature in the energy management application and keep both values synchronized at all times.


Supported models

  • AC-THOR 3kW

Did this answer your question?