Before you start
Before you begin, make sure:
The charging station is physically installed and powered on
The INCH Duo is updated to the latest software version
Step-by-Step Instructions
1. Connect the charging station to the network
Connect an Ethernet cable to the Ethernet port on the INCH Duo
Verify the connection is established by checking the LED on the charging station
For network infrastructure requirements and troubleshooting, see Infrastructure requirements for the gateway.
[Schematic image will be placed here]
2. Access the charging station settings
Open a web browser and navigate to the INCH Duo web portal at
https://[chargerIP]orhttps://[chargerserial].localLog in with the web portal credentials
3. Enable communication via Modbus
By default, Modbus ports are disabled on the INCH Duo for security reasons. You need to enable them to allow the gateway to communicate with the charging station.
Navigate to:
ETREL → Configuration → Connectivity → Smart home/building connectivityEnable both Modbus communication enabled options to activate port
502Configure the following settings:
Communication fail fallback current:
Navigate to:
ETREL → Configuration → Power Management → General ConfigurationConfigure the following. Power Management Configuration settings:
Charger involved in power management:
Disabled
Click Save and reboot the charging station
4. Discover the charging station in the commissioning wizard
The charging station is now ready for the commissioning wizard. The gateway will scan the network to find available devices, which may take a few minutes. Once complete, the Etrel INCH Duo charging station will appear on the results page.
FAQ
Why isn't the charging station appearing in the Xenon Dashboard?
Check that the charging station is connected via Ethernet and that both Modbus communication options are enabled in the web portal under Connectivity → Smart home/building connectivity. Restart the gateway and wait for the network scan to complete.
How do I update the firmware of the charging station?
You can perform the update through the Etrel web portal.
For detailed update instructions, refer to the official Etrel documentation.
What are the factory default login credentials?
The factory default credentials are:
Username: [email protected]
Password: toor
Change the default password after your first login to secure the device.
What if I have forgotten the password?
Perform a factory reset on the device to restore the original factory state. Refer to the manufacturer's documentation for reset instructions.
Why do I need to disable Smart power management?
The INCH Duo's built-in smart power management conflicts with the gateway's energy management system. Disabling it ensures the gateway can control the charging output according to the energy optimization settings.
What is the fallback current and how should I set it?
The fallback current is the maximum charging current the INCH Duo uses if communication with the gateway is lost. Set it to a value that complies with your installation's electrical specifications and local regulations.
Supported models
INCH Duo